NameLighting and Appliance Panelboard - 400V MCB - Surface
Category23-35 31 29 : Switchboards
DescriptionLighting and Appliance Panelboard - 400V MCB - Surface_400 A
Installed ByContractor
ManufacturerE&I Engineering Ltd
ModelNumberLV Switchboard  (video search)
Reference26 24 16.A

4 items found
PropertyValueUnit
Ballast Voltage600V
L.A.P. Depth146.1n/a
L.A.P. Height1574.8n/a
L.A.P. Width508n/a


3 items found
DocumentTypeStatusDescription
SubmittalFile-154113DT : Data SheetApprovedActi9 Isobar P B - distribution board
SubmittalFile-154123IM : Installation ManualApprovedQuick smart installations
SubmittalFile-154133DT : Data SheetApprovedMCB Various Accessories

Not Available
Mfg. Warranty Descriptionn/a
Mfg. Parts POCn/a
Mfg. Parts Durationn/a
Mfg. Labor POCn/a
Mfg. Labor Durationn/a

Extended Warranty POCn/a
Ext. Durationn/a

Not Available
PartDescriptionRcmd / CriticalSupplierPart No.
(none found)

Frequency: 12 months
TaskDescriptionDuration
1Mechanism - Check theMCHgear motor charging time at 0.85 Un5 minutes
2Mechanism - Check the general condition of the mechanism5 minutes
3Mechanism - Check the number of device operating cycles5 minutes
4Breaking unit (arc chutes + contacts) - Check the condition of the breaking unit5 minutes
5Breaking unit (arc chutes + contacts) - Check mounting of arc chutes and filter cleanliness5 minutes
6Auxiliaries - Check operation of indication contacts (OF,PF)5 minutes
7Auxiliaries - Check closing operation withXFclosing voltage release at 0.85 Un5 minutes
8Auxiliaries - Check opening operation withMXopening voltage release at 0.70 Un5 minutes
9Auxiliaries - Check closing and opening operations withMNundervoltage release5 minutes
10Auxiliaries - Check time delay ofMNRdelayed undervoltage release5 minutes
11Control unit - Check microswitchesOF/SDE/PF/CH5 minutes
12Control unit - CheckM2Cprogrammable contacts5 minutes
13Control unit - Save protection settings, reports, and event logs withEcoStruxure Power Commissionsoftware5 minutes
14Control unit - Check overcurrent protection5 minutes
15Chassis - Check operation ofCD,CT,CEposition contacts andEFauxiliary contacts5 minutes
16Chassis - Check operation of safety shutters5 minutes
17Chassis - Clean chassis and check presence of grease on chassis5 minutes
18Chassis - Check disconnecting contact clusters5 minutes
19Power connections - Check connection system5 minutes
20Device - Check the general condition of the device5 minutes
21Mechanism - Operate the device manually and electrically5 minutes
22Mechanism - Charge the device electrically withMCHgear motor5 minutes
23Mechanism - Check the complete closing of device poles5 minutes
24Auxiliaries - Check auxiliary wiring and insulation5 minutes
25Control Unit - Check device tripping and operation of SDE fault-trip indication contacts5 minutes
26Control Unit - Check ground-fault (MicroLogic 6.0 X) or earth-leakage (MicroLogic 7.0 X) protection function5 minutes
27Control Unit - Check operation of Energy Reduction Maintenance Settings (ERMS)5 minutes
28Device locking - Operate device keylocks5 minutes
29Device locking - Operate device padlocks5 minutes
30Chassis - Check device racking operation5 minutes
31Chassis - Check IBPO racking interlock between racking handle and opening pushbutton (MasterPact MTZ2/MTZ3)5 minutes
32Chassis - Check EIFE chassis position limit switches5 minutes
33Chassis locking - Operate chassis keylocking system5 minutes
34Chassis locking - Operate chassis padlocking system5 minutes
35Mechanical interlocking - Operate interlocking systems5 minutes

Frequency: 60 months
TaskDescriptionDuration
1Device - Measure insulation resistance5 minutes
2Mechanism - Check opening and closing forces5 minutes
3Mechanism - Clean and regrease the mechanism5 minutes
4Breaking Unit - Measure the contact resistance for each pole5 minutes
5Auxiliaries - Check opening time ofMXopening voltage release5 minutes
6Auxiliaries - Check closing time ofXFclosing voltage release5 minutes
7Auxiliaries - Preventively replace theXF,MX,MNvoltage releases5 minutes
8Auxiliaries - Preventively replaceMicroLogic Xcontrol unit and electrronic modules5 minutes
9Control unit - Diagnose the performance of theMicroLogic Xcontrol unit functions5 minutes
10Control unit - Preventively replace theMicroLogic Xcontrol uni5 minutes
11Chassis - Check connection/disconnection torque5 minutes
12Chassis - Clean and regrease chassis ofMasterPactdrawout devices5 minutes
13Communication system - Check data transmission over theIFEEthernetinterface orEIFEembeddedEthernetinterface5 minutes
14Mechanical interlocking - Operate mechanical interlocking by cable5 minutes
15Mechanical interlocking - Operate mechanical interlocking by rod5 minutes

Frequency: 12 months
TaskDescriptionDuration
1DANGER - HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH0 minutes
2Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E or CSA Z462 or local equivalent.0 minutes
3This equipment must be installed and serviced by qualified electrical personnel.0 minutes
4Turn off all power supplying this equipment before performing maintenance inspections. Assume that all circuits are live until they are de-energized, tested, grounded, and tagged. Consider all sources of power, including the possibility of backfeeding and control power.0 minutes
5Always use a properly rated voltage sensing device to confirm that power is off.0 minutes
6Replace all devices, doors, and covers before turning on power to this equipment.0 minutes
7Beware of potential hazards and carefully inspect the work area for tools and objects that may have been left inside the equipment.0 minutes
8Failure to follow these instructions will result in death or serious injury.0 minutes